Cart()
 
 
Categories
Contact Us
  • A&S Power Supply Co.,Ltd
  • Address:469, Xinsheng Road, Gaoxin District, Chengdu, Sichuan, China
  • Tel:+86-28-65376776
  • Fax:+86-28-86129221
  • Email:inverter@electrical8.com
  • Contact Person:Karina
Home / Products / UPS Power Supply / Riello UPS Power Supply / Riello Master HP UPS MHT 250

Riello Master HP UPS MHT 250

Riello Master HP UPS MHT 250
share

Specifications
INPUT
Rated power 250000 VA
Voltage 400 Vac three-phase Vac
Voltage tolerance + 20% - 25%
Frequency 50/60 Hz with autorange
Frequency tolerance 45/65 Hz
Power factor 0,99
Input current 352 A
Current distorsion <3%
Soft start 0-100% in 10
BY PASS
Rated voltage 400 Vac three-phase selectable 380 and 415
Voltage tolerance ± 15% (selectable from ± 10% to ± 25% from front panel)
Rated frequency 50/60 Hz (autorange)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Rated current 352 A
Number phases 3
Back-feed protection yes
Overload capacity Inx10ms 14
OUTPUT and INVERTER OUTPUT
Rated power 250000 VA
Active power 225000 W
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Dynamic stability ± 5% in 5 ms
Frequency same as the input (autorange)
Voltage distortion with distorcing load <3%
Voltage distortion with linear load <1%
Frequency stability ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present
Inverter efficiency at rated load 95 %
Overload 125% 150% 200% of the rated current for 10' / 1' / 7

Riello Vision UPS VST 800
Riello Vision UPS VST 800
Specifications:INPUTRated power 800 VAVoltage 230 VacFrequency 50/60 Hz with autorangeFrequency tolerance ± 5%OUTPUT and INVERTER OUTPUTRated power 800 VAActive power 540 WNumber phases 1Waveform SinewaveFrequency 50/60 Hz with autorange
Riello Master FC400 UPS MFC 120
Riello Master FC400 UPS MFC 120
Specifications: SKU MFC120 Power 120kVA/96kW Runtime Add external battery extension Input Connection Hardwired terminals Input Voltage 380/400/415Vac 3phase, 45-65Hz Output Connection Hardwired terminals Output Voltage 208Vac 3phase+N +/-1%, 400Hz +/- 0.05% Dimensions (WxDxH) 550x740x1200mm
Riello Multi Sentry UPS MST 20
Riello Multi Sentry UPS MST 20
Specifications:INPUTRated power 20000 VAVoltage 400 Vac three-phase + N VacVoltage tolerance ± 20%Frequency tolerance 40/72 HzPower factor 0.99BY PASSRated voltage 400Voltage tolerance ± 15% (selectable from ± 5% to ± 25%)Rated frequency 50/60 HzFrequency tolerance ± 5% (selectable from ± 0.25
Riello Sentinel Pro UPS SEP 3000 ER
Riello Sentinel Pro UPS SEP 3000 ER
Specifications:INPUTRated power 3000 VAVoltage 220-230-240 VacVoltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOADFrequency 50/60 HzFrequency tolerance 50 Hz ± 5% / 60 Hz ± 5%Power factor > 0.99Current distorsion ≤7%BY PASSVoltage tolerance 180 - 264Frequency
Riello Master MPS UPS MPT 80
Riello Master MPS UPS MPT 80
Specifications: INPUT Voltage 380 - 400 - 415 Vac three-phase Vac Frequency 45 - 65 Hz Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel) Soft start 0 - 100% in 120’’ (selectable) Voltage Range 400 V + 20% /- 25% BY PASS Rated voltage 380 - 400 - 415 Vac three-ph
Riello Master MPS UPS MPT 20
Riello Master MPS UPS MPT 20
Specifications:INPUTVoltage 380 - 400 - 415 Vac three-phase VacFrequency 45 - 65 HzFrequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)Soft start 0 - 100% in 120’’ (selectable)Voltage Range 400 V + 20% /- 25%BY PASSRated voltage 380 - 400 - 415 Vac three-phase + NRated fre
Riello Sentinel Dual (High Power) UPS SDL 6500 TM
Riello Sentinel Dual (High Power) UPS SDL 6500 TM
Specifications:INPUTRated power 6500 VAVoltage 380-400-415 VacFrequency 50/60 Hz ± 5 HzPower factor >0.98Current distorsion ≤5%BY PASSVoltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)Frequency tolerance Selected frequency ± 5% (user configurable)OUTPUT and INVERTE
Riello Sentinel Power Green UPS SPM 6
Riello Sentinel Power Green UPS SPM 6
Specifications:INPUTVoltage 220-230-240 VacFrequency 50/60 Hz +/- 10 HzBY PASSVoltage tolerance 160 - 276 Vac (selectable in Economy Mode or Smart Active Mode)Frequency tolerance Selected frequency ±10%OUTPUT and INVERTER OUTPUTRated power 6000 VAActive power 5400 WWaveform SinusoidalOVERLOAD TIMES
Riello Master HP UPS MHT 160
Riello Master HP UPS MHT 160
SpecificationsINPUTRated power 160000 VAVoltage 400 Vac three-phase VacVoltage tolerance + 20% - 25%Frequency 50/60 Hz with autorangeFrequency tolerance 45/65 HzPower factor 0,99Input current 226 ACurrent distorsion
Riello Sentinel Dual (Low Power) UPS SDH 3000
Riello Sentinel Dual (Low Power) UPS SDH 3000
Specifications:INPUTRated power 3000 VAVoltage 220-230-240 VacVoltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOADFrequency 50/60 HzFrequency tolerance 50 Hz ± 5% / 60 Hz ± 5%Power factor > 0.99Current distorsion ≤7%BY PASSVoltage tolerance 200 - 253Frequency