Specifications:
General
Bypass Connection 5 wire (3PH + N + G)
Bypass Voltage Tolerance +/- 15%
Max Bypass Input Current 139A
Output
Output Power Capacity 40 kW / 50 kVA
Max Configurable Power 40 kW / 50 kVA
Nominal Output Voltage 208V 3PH
Efficiency at Full Load 89.0%
Output Voltage Distortion Less than 3%
Output Frequency (sync to mains) 60Hz +/- 3 Hz
Crest Factor 2.5 : 1
Topology Double Conversion Online
Waveform Type Sine wave
Output Connections
(1) Hard Wire 5-wire (3PH + N + G)
Output Voltage Tolerance +/-1% static and +/- 5% at 100% load step
Output Voltage THD < 1% linear load and < 2.5% nonlinear load
Overload Operation 60 seconds @ 130% and 30 seconds @ 145%
Efficiency at Half Load 89.0%
Required Output Current Protection 175A
Bypass Built-in Static Bypass
Input
Nominal Input Voltage 208V 3PH
Input Frequency 60 Hz +/- 5 Hz
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations 177 - 239 (208V)V
Maximum Input Current 150A
Input Breaker Capacity 200 A
Input Total Harmonic Distortion Less than 3% for full load
Type of Input Protection Required 3-pole breaker

APC Smart-UPS SUA1000XL
APC Smart-UPS SUA1000XL
Specifications:OutputOutput Power Capacity 800 Watts / 1000 VAMax Configurable Power 800 Watts / 1000 VANominal Output Voltage 120VOutput Voltage Distortion Less than 5% at full loadOutput Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal, 57 - 63 Hz for 60 Hz nominalTopology Line InteractiveWa
APC MGE EPS 8000 UPS E8TUPS750
APC MGE EPS 8000 UPS E8TUPS750
Specifications:GeneralBypass Connection 4 wire (3Ph + N) or 5 wire (3Ph + N + G)Bypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%Max Bypass Input Current 1140AOutputOutput Power Capacity 675 kW / 750 kVAMax Configurable Power 675 kW / 750 kVANominal Output Voltage 480V 3PH, 600V 3PHEffi
APC Smart-UPS VT SUVTP20KF4B4S
APC Smart-UPS VT SUVTP20KF4B4S
Specifications:OutputOutput Power Capacity 16 kW / 20 kVAMax Configurable Power 16 kW / 20 kVANominal Output Voltage 120V, 208V, 208V 3PHOutput Voltage Note Configurable for 208 and 220V - 3 PhaseEfficiency at Full Load 93.8%Output Voltage Distortion Less than 5% at full loadOutput Frequency (sync t
APC Back-UPS BX1100U-LM
APC Back-UPS BX1100U-LM
Back-UPS specification: Output Power Capacity 660 Watts / 1100 VA Max Configurable Power 660 Watts / 1100 VA Nominal Output Voltage 120V Efficiency at Full Load 97.0% Output Frequency (sync to mains) 50/60Hz +/- 3 Hz Topology Line Interactive Waveform Type Stepped approximation to a sinewave
APC MGE Galaxy 3500 UPS G35T30KH4B4S
APC MGE Galaxy 3500 UPS G35T30KH4B4S
Specifications:OutputOutput Power Capacity 24 kW / 30 kVAMax Configurable Power 24 kW / 30 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 95.8%Output Voltage Distortion Less than 5%Output Frequency (sync
APC Symmetra PX UPS SY125K500DR-PD
APC Symmetra PX UPS SY125K500DR-PD
Specifications:GeneralBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%OutputOutput Power Capacity 125 kW / 125 kVAMax Configurable Power 500 kW / 500 kVANominal Output Voltage 400V 3PH, 480V 3PHOutput Voltage Distortion Less than 2%Output Frequency (sync to mains) 50 Hz, 60 HzOther Out
APC Back-UPS BX650U-LM
APC Back-UPS BX650U-LM
Back-UPS specification:Output Power Capacity 390 Watts / 650 VAMax Configurable Power 390 Watts / 650 VANominal Output Voltage 120VOutput Frequency (sync to mains) 50/60Hz +/- 3 HzTopology Line InteractiveWaveform Type Stepped approximation to a sinewaveOutput Connections(4) NEMA 5-15R (Battery Back
APC Symmetra UPS SYH2K6RMT
APC Symmetra UPS SYH2K6RMT
Specifications:OutputOutput Power Capacity 1400 Watts / 2000 VAMax Configurable Power 4200 Watts / 6000 VANominal Output Voltage 208VOutput Voltage Note Configurable for 208 or 240 nominal output voltageEfficiency at Full Load 91.0%Output Voltage Distortion Less than 5% at full loadOutput Frequency
APC MGE Galaxy 5000 UPS SUG580S90UL
APC MGE Galaxy 5000 UPS SUG580S90UL
Specifications:OutputOutput Power Capacity 72 kW / 80 kVAMax Configurable Power 72 kW / 0 VANominal Output Voltage 480V 3PH, 600V 3PHEfficiency at Full Load 92.8%Output Voltage Distortion Less than 2%Output Frequency (sync to mains) 60 HzCrest Factor 3 : 1Topology Double Conversion OnlineWaveform Ty
APC Smart-UPS VT SUVTR20KF4B5S
APC Smart-UPS VT SUVTR20KF4B5S
Specifications:OutputOutput Power Capacity 16 kW / 20 kVAMax Configurable Power 16 kW / 20 kVANominal Output Voltage 120V, 208V, 208V 3PHOutput Voltage Note Configurable for 200 : 208 or 220V 3 Phase nominal output voltageOutput Voltage Distortion Less than 5% at full loadOutput Frequency (sync to m