Cart()
 
 
Categories
Contact Us
  • A&S Power Supply Co.,Ltd
  • Address:469, Xinsheng Road, Gaoxin District, Chengdu, Sichuan, China
  • Tel:+86-28-65376776
  • Fax:+86-28-86129221
  • Email:inverter@electrical8.com
  • Contact Person:Karina
Home / Products / power supply / Omron Power Supply / S8VS / Omron Power Supply S8VS Series S8VS-09024AS-F

Omron Power Supply S8VS Series S8VS-09024AS-F

Omron Power Supply S8VS Series S8VS-09024AS-F
share

Total Run Time Monitor , Input 100 to 240 VAC , 90 W , Output 24 V 3.75 A , With Undervoltage Alarm (Ttransistor (Sourcing))
Power rating 90 W
Efficiency 83% TYP. ï¼ˆAt 100 VAC input)85% TYP. ï¼ˆAt 200 VAC input)
Rated input voltage 100 to 240 VAC
Allowable-input voltage variable range 85 to 264 VAC80 to 370 VDC
Note at DC input The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency 50/60 Hz (47 to 450 Hz Single-phase)
Rated input current 1.9 A TYP. ï¼ˆAt 100 VAC input)1.2 A TYP. ï¼ˆAt 200 VAC input)
Harmonic Current EN61000-3-2
Leakage current 0.5 mA Max. (At 100 VAC input)1.0 mA Max. (At 200 VAC input)
Inrush current 14 A TYP. ï¼ˆAt 100 VAC input (For cold start at 25 CEL))28 A TYP. ï¼ˆAt 200 VAC input (For cold start at 25 CEL))
Rated output voltage 24 VDC
Output voltage variable range -10 to +15% (With V. ADJ)(The output voltage may increase beyond the allowable voltage range (up to +15% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.)
Ripple 2%(p-p) Max. (Under the rated I/O conditions.)150 mV Max. (Under the rated I/O conditions.)
Static input variation influence 0.5% Max. (At 85 to 264 VAC input, 100% load)
Static load variation influence 1.5% Max. (At rated input, 0 to 100% load)
Ambient temperature variation influence 0.05 %/CEL Max.
Rated output current 3.75 A
Start up time 660 ms TYP. ï¼ˆ100 VAC input)420 ms TYP. ï¼ˆ200 VAC input)
Hold time 28 ms TYP. ï¼ˆ100 VAC input)136 ms TYP. ï¼ˆ200 VAC input)
Overload protection 105% to 160% of the rated output currentInverted L voltage drop, Intermittent operation, Automatic reset
Overvoltage protection Operated at 130% Min. of the rated output voltage, Shut-offResetting: Reset the power by turning it back (OFF time: at least 3 min)
Overheat protection No
Output voltage indication Yes (Resolution: 0.1 V / Accuracy: +/- 2% (percentage of output voltage value) +/- 1 digit Max.)
Output current indication Yes (Resolution: 0.1 A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max.)
Peak-hold current indication Yes (Resolution: 0.1 A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max. / Minimum detectable signal width: 10 ms (20 ms Max.))
Maintenance forecast monitor output No
Total run time monitor indication Yes (Resolution: 1 kh / Setting range: 1 to 150 kh)
Total run time monitor output Yes (open collector output), 30 VDC Max., 50 mA Max., Sourcing (PNP)
Undervoltage alarm indication Yes (Resolution: 0.1 V / Setting range: 18.5 to 27.5 V)
Undervoltage alarm output Yes (open collector output), 30 VDC Max., 50 mA Max., Sourcing (PNP)
Power failure alarm output No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (Up to 2 Power Supplies with external diode)
Remote sensing function No
Applicable standard (UL) Standard No.: UL Listed: UL508 (Listing), UL UR: UL60950-1 (Recognition)
Applicable standard (CSA) Standard No.: cUL: CSA C22.2 No.107.1, cUR: CSA C22.2 No.60950-1
Applicable standard (EN) Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMI)) Emission Enclosure: Conforms to EN61204-3 Class AEmission AC mains: Conforms to EN61204-3 Class A and based on FCC Class AEMS: EN61204-3 High severity levels
Applicable standard(VDE) Standard No.: VDE0160, VDE0805 Teil 1 File number:
Applicable standard(SEMI) F47-0200 (200 VAC input)
Ambient temperature Operating: -10 to 60 CELStorage: -25 to 65 CEL(with no icing or condensation)
Ambient humidity Operating: 25 to 85%Storage: 25 to 90%(With no icing or condensation)
Dielectric strength Between all inputs and all outputs/alarm outputs: 3 kVAC for 1 min (Detection current: 20 mA)Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)Between all outputs/alarm outputs and all PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)Between all outputs and all alarm outputs: 500 VAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs/alarm outputs and all inputs/PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Natural air-cooling
Construction Covered type
Terminal type Screw terminal
Mounting type DIN Rail mounting type
Weight 490 g Max.

Omron Power Supply S8VS Series S8VS-12024BE
Omron Power Supply S8VS Series S8VS-12024BE
Standard Model , Input 100 to 240 VAC , 30 W , Output 12 V 2.5 APower rating 30 WEfficiency 81% TYP. ï¼ˆAt 100 VAC input)80% TYP. ï¼ˆAt 200 VAC input)Rate
Omron S8JX Switch Mode Power S8JX-G03548CD
Omron S8JX Switch Mode Power S8JX-G03548CD
Covered type , Input 100 to 240 VAC , 35 W , Output 48 V 0.75 A , DIN Rail mounting typePower rating 35 WEfficiency 73% Min.Rated input voltage 100 to 240 
Omron S8JX Switch Mode Power S8JX-G01524
Omron S8JX Switch Mode Power S8JX-G01524
Open-Frame Type , Input 100 to 240 VAC , 15W , Output 24V 0.65A , Front-mounting typeAs of November 15, 2012Power rating 15 WEfficiency 68% Min.Rated input voltage 100 to
Omron Power Supply S8JX Switch Mode Power S8JX-P30024CD
Omron Power Supply S8JX Switch Mode Power S8JX-P30024CD
Covered type , Input 100 to 240 VAC , 300W , Output 24V 14A , DIN Rail mounting typePower rating 300 WEfficiency 79% Min.Rated input voltage 100 to 240 VACAllowable-input
Omron Power Supply S8TX Series S8TS-06024F
Omron Power Supply S8TX Series S8TS-06024F
Basic Block , Connector Terminal Type , Input 100 to 240 VAC , Output 24 V 2.5 APower rating 60 WEfficiency 80% TYP. ï¼ˆAt rated input, 100% load)Rated input volt
Omron S8JX Switch Mode Power S8JX-P05024D
Omron S8JX Switch Mode Power S8JX-P05024D
Open-Frame Type , Input 100 to 240 VAC , 50W , Output 24V 2.1A , DIN Rail mounting typePower rating 50 WEfficiency 77% Min.Rated input voltage 100 to 240 VACAllowable-inp
Omron S8JX Switch Mode Power S8JX-G01548D
Omron S8JX Switch Mode Power S8JX-G01548D
Open-Frame Type , Input 100 to 240 VAC , 15W , Output 48V 0.35A , DIN Rail mounting typeAs of November 15, 2012Power rating 15 WEfficiency 68% Min.Rated input voltag
Omron Power Supply S8JX Switch Mode Power S8JX-P10024
Omron Power Supply S8JX Switch Mode Power S8JX-P10024
Open-Frame Type , Input 100 to 240 VAC , 100W , Output 24V 4.5A , Front-mounting typePower rating 100 WEfficiency 81% Min.Rated input voltage 100 to 240 VACAllowable-input vol
Omron Power Supply S8VM Series S8VM-10015CD
Omron Power Supply S8VM Series S8VM-10015CD
Standard Type , Covered Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 100 W , Output 15 V 7 APower rating 100 WEfficiency 81% Min.Rated in
Omron S8JX Switch Mode Power S8JX-G01548
Omron S8JX Switch Mode Power S8JX-G01548
Open-Frame Type , Input 100 to 240 VAC , 15W , Output 48V 0.35A , Front-mounting typeAs of November 15, 2012Power rating 15 WEfficiency 68% Min.Rated input voltage 100 to