Omron Power Supply S8VS Series S8VS-18024

Omron Power Supply S8VS Series S8VS-18024
share

Standard Model , Input 100 to 240 VAC , 180 W , Output 24 V 7.5 A
Power rating 180 W
Efficiency 85% TYP. ï¼ˆAt 100 VAC input)88% TYP. ï¼ˆAt 200 VAC input)
Rated input voltage 100 to 240 VAC
Allowable-input voltage variable range 85 to 264 VAC80 to 370 VDC
Note at DC input The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency 50/60 Hz (47 to 63 Hz Single-phase)
Rated input current 2.2 A TYP. ï¼ˆAt 100 VAC input)1.1 A TYP. ï¼ˆAt 200 VAC input)
Power factor 0.9 Min.
Harmonic Current EN61000-3-2
Leakage current 0.5 mA Max. (At 100 VAC input)1.0 mA Max. (At 200 VAC input)
Inrush current 14 A TYP. ï¼ˆAt 100 VAC input (For cold start at 25 CEL))28 A TYP. ï¼ˆAt 200 VAC input (For cold start at 25 CEL))
Rated output voltage 24 VDC
Output voltage variable range -10 to +15% (With V. ADJ)(The output voltage may increase beyond the allowable voltage range (up to +15% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.)
Ripple 2%(p-p) Max. (Under the rated I/O conditions.)50 mV Max. (Under the rated I/O conditions.)
Static input variation influence 0.5% Max. (At 85 to 264 VAC input, 100% load)
Static load variation influence 1.5% Max. (At rated input, 0 to 100% load)
Ambient temperature variation influence 0.05 %/CEL Max.
Rated output current 7.5 A
Start up time 570 ms TYP. ï¼ˆ100 VAC input)470 ms TYP. ï¼ˆ200 VAC input)
Hold time 58 ms TYP. ï¼ˆ100 VAC input)62 ms TYP. ï¼ˆ200 VAC input)
Overload protection 105% to 160% of the rated output currentInverted L voltage drop, Automatic reset
Overvoltage protection Operated at 115 to 150 % of the rated output voltage, Shut-offResetting: Reset the power by turning it back (OFF time: at least 3 min)
Overheat protection No
Maintenance forecast monitor output No
Total run time monitor output No
Undervoltage alarm output No
Power failure alarm output No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (Up to 2 Power Supplies with external diode)
Remote sensing function No
Applicable standard (UL) Standard No.: UL Listed: UL508 (Listing), UL UR: UL60950-1 (Recognition)
Applicable standard (CSA) Standard No.: cUL: CSA C22.2 No.107.1, cUR: CSA C22.2 No.60950-1
Applicable standard (EN) Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMI)) EMI: EN61204-3 Class BEmission Enclosure: Conforms to EN55011 Group 1 Class BEmission AC mains: Conforms to EN55011 Group 1 Class B and based on FCC Class AEMS: EN61204-3 High severity levels
Applicable standard(VDE) Standard No.: VDE0160, VDE0805 Teil 1 File number:
Applicable standard(SEMI) F47-0200 (200 VAC input)
Ambient temperature Operating: -10 to 60 CELStorage: -25 to 65 CEL(with no icing or condensation)
Ambient humidity Operating: 25 to 85%Storage: 25 to 90%(With no icing or condensation)
Dielectric strength Between all inputs and all outputs/alarm outputs: 3 kVAC for 1 min (Detection current: 20 mA)Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)Between all outputs/alarm outputs and all PE terminals: 1 kVAC for 1 min (Detection current: 30 mA)Between all outputs and all alarm outputs: 500 VAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs/alarm outputs and all inputs/PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Natural air-cooling
Construction Covered type
Terminal type Screw terminal
Mounting type DIN Rail mounting type
Weight 850 g Max.

Omron S8JX Switch Mode Power S8JX-G15048C
Omron S8JX Switch Mode Power S8JX-G15048C
Covered type , Input 100 to 240 VAC , 150 W , Output 48 V 3.3 A , Front-mounting type Power rating 150 W Efficiency 85% Min. Rated input voltage 100 to 240 VAC A
Omron Power Supply S8JX Switch Mode Power S8JX-P15005D
Omron Power Supply S8JX Switch Mode Power S8JX-P15005D
Open-Frame Type , Input 100 to 240 VAC , 150W , Output 5V 30A , DIN Rail mounting typePower rating 150 WEfficiency 79% Min.Rated input voltage 100 to 240 VACAllowable-inp
Omron Power Supply S8VS Series S8VS-09024A
Omron Power Supply S8VS Series S8VS-09024A
andard Model , Input 100 to 240 VAC , 90 W , Output 24 V 3.75 A , Screwless Terminal BlockPower rating 90 WEfficiency 83% TYP. ï¼ˆAt 100 VAC input)84% TYP.&n
Omron Power Supply S8VS Series S8VS-24024BP
Omron Power Supply S8VS Series S8VS-24024BP
Total Run Time Monitor , Input 100 to 240 VAC , 240 W , Output 24 V 10 A , With Undervoltage Alarm (Ttransistor (Sourcing))Power rating 240 WEfficiency 85% TYP. 
Omron Power Supply S8VM Series S8VM-03024A
Omron Power Supply S8VM Series S8VM-03024A
Undervoltage Alarm Type , Covered Type , Bottom Mounting Type , Input 100 to 240 VAC , 30 W , Output 24 V 1.3 APower rating 30 WEfficiency 81% Min.Rated input&n
Omron S8JX Switch Mode Power S8JX-G01505D
Omron S8JX Switch Mode Power S8JX-G01505D
Open-Frame Type , Input 100 to 240 VAC , 15W , Output 5V 3A , DIN Rail mounting typePower rating 15 WEfficiency 68% Min.Rated input voltage 100 to 240 VACAllowable-input&
Omron Power Supply S8VS Series S8VS-03024
Omron Power Supply S8VS Series S8VS-03024
Total Run Time Monitor , Input 100 to 240 VAC , 120 W , Output 24 V 5 APower rating 120 WEfficiency 83% TYP. ï¼ˆAt 100 VAC input)85% TYP. ï¼ˆAt 200 V
Omron Power Supply S8VM Series S8VM-10024CD
Omron Power Supply S8VM Series S8VM-10024CD
Standard Type , Open-Frame Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 100 W , Output 24 V 4.5 APower rating 100 WEfficiency 82% Min.Rated&nb
Omron Power Supply S8EX Series S8EX-BP10048
Omron Power Supply S8EX Series S8EX-BP10048
Open type , Input 100 to 240 VAC , 100W , Output 48V 2.1APower rating 100 WEfficiency 84% Min. ï¼ˆAt 100 VAC input)86% Min. ï¼ˆAt 200 VAC input)Rated in
Omron S8JX Switch Mode Power S8JX-P10012
Omron S8JX Switch Mode Power S8JX-P10012
Open-Frame Type , Input 100 to 240 VAC , 100W , Output 12V 8.5A , Front-mounting typePower rating 100 WEfficiency 78% Min.Rated input voltage 100 to 240 VACAllowable-input vol