Specifications:
Output
Output Power Capacity 32 kW / 40 kVA
Max Configurable Power 32 kW / 40 kVA
Nominal Output Voltage 400V 3PH
Output Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load 95.8%
Output Voltage Distortion Less than 5%
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal
Other Output Voltages 380, 415
Crest Factor Unlimited
Topology Double Conversion Online
Waveform Type Sine wave
Output Connections
(1) Hard Wire 4-wire (3PH + G)
(1) Hard Wire 5-wire (3PH + N + G)
(1) Screw Terminals
Output Voltage Tolerance +/-1% static and +/- 5% at 100% load step
Output Voltage THD < 2% for 0 to 100% linear load and < 5% for full non linear load
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load 95.5%
Required Output Current Protection 63A
Bypass Built-in Maintenance Bypass, Built-in Static Bypass
Input
Nominal Input Voltage 400V 3PH
Input Frequency 40 - 70 Hz (auto sensing)
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations 304 - 477V
Input voltage adjustable range for mains operation 340 - 460 (400V)V
Other Input Voltages 380, 415
Maximum Input Current 54A
Input Breaker Capacity 63 A
Input Total Harmonic Distortion Less than 5% for full load
Type of Input Protection Required 3-pole breaker

APC Smart-UPS SURT15KRMXLT
APC Smart-UPS SURT15KRMXLT
Specifications:OutputOutput Power Capacity 12 kW / 15 kVAMax Configurable Power 12 kW / 15 kVANominal Output Voltage 208VOutput Voltage Note Configurable for 208 or 240 nominal output voltageOutput Voltage Distortion Less than 5%Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/-
APC Back-UPS BH500NET
APC Back-UPS BH500NET
Back-UPS specification:Output Power Capacity 300 Watts / 500 VAMax Configurable Power 300 Watts / 500 VANominal Output Voltage 120VTopology StandbyOutput Connections(4) NEMA 5-15R (Battery Backup) NEMA 5-15RInputNominal Input Voltage 120VInput Frequency 47 - 63 HzInput ConnectionsNEMA 5-15P NEMA 5-1
APC MGE Galaxy 3500 UPS G35T20KF2B4S
APC MGE Galaxy 3500 UPS G35T20KF2B4S
Specifications:OutputOutput Power Capacity 16 kW / 20 kVAMax Configurable Power 16 kW / 20 kVANominal Output Voltage 208V 3PHOutput Voltage Note Configurable for 200 : 208 or 220V 3 Phase nominal output voltageEfficiency at Full Load 93.4%Output Voltage Distortion Less than 3%Output Frequency (sync
APC Smart-UPS SURTD5000RMXLI
APC Smart-UPS SURTD5000RMXLI
Specifications:OutputOutput Power Capacity 16 kW / 20 kVAMax Configurable Power 16 kW / 20 kVANominal Output Voltage 208VOutput Voltage Note Configurable for 208 or 240 nominal output voltageOutput Voltage Distortion Less than 5%Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/-
APC Symmetra PX UPS SY250K500D
APC Symmetra PX UPS SY250K500D
Specifications:GeneralBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%OutputOutput Power Capacity 250 kW / 250 kVAMax Configurable Power 500 kW / 500 kVANominal Output Voltage 400V 3PH, 480V 3PHOutput Voltage Distortion Less than 2%Output Frequency (sync to mains) 50 Hz, 60 HzOther Out
APC MGE Galaxy 3500 UPS G35TSBPAR10K15F
APC MGE Galaxy 3500 UPS G35TSBPAR10K15F
Specifications:Nominal Output Voltage 208V 3PHInputNominal Input Voltage 208V 3PHInput Frequency 60 HzPhysicalNet Weight 121.82 KGMaximum Height 1486.00 mmMaximum Width 356.00 mmMaximum Depth 838.00 mmShipping Weight 156.36 KGShipping Height 1663.00 mmShipping Width 723.00 mmShipping Depth 1104.00 m
APC Symmetra PX UPS SY96K160H-PD
APC Symmetra PX UPS SY96K160H-PD
Specifications:GeneralBypass Connection 5 wire (3PH + N + G)Max Bypass Input Current 250ABypass Protection Device 250AOutputOutput Power Capacity 96 kW / 96 kVAMax Configurable Power 160 kW / 160 kVANominal Output Voltage 230V, 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase
APC Symmetra PX UPS SY500K500DL-PD
APC Symmetra PX UPS SY500K500DL-PD
Specifications:GeneralBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%OutputOutput Power Capacity 500 kW / 500 kVAMax Configurable Power 500 kW / 500 kVANominal Output Voltage 400V 3PH, 480V 3PHOutput Voltage Distortion Less than 2%Output Frequency (sync to mains) 50 Hz, 60 HzOther Out
APC Smart-UPS SUA3000XL
APC Smart-UPS SUA3000XL
Specifications:OutputOutput Power Capacity 2700 Watts / 3000 VAMax Configurable Power 2700 Watts / 3000 VANominal Output Voltage 120VEfficiency at Full Load 96.0%Output Voltage Distortion Less than 5% at full loadOutput Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal, 57 - 63 Hz for 60 Hz nom
APC Back-UPS BE550G
APC Back-UPS BE550G
Back-UPS specification:Output Power Capacity 330 Watts / 550 VAMax Configurable Power 330 Watts / 550 VANominal Output Voltage 120VOutput Frequency (sync to mains) 50/60Hz +/- 3 HzTopology StandbyWaveform Type Stepped approximation to a sinewaveOutput Connections(4) NEMA 5-15R (Battery Backup) NEMA