Omron S8JX Switch Mode Power S8JX-G03505C

Omron S8JX Switch Mode Power S8JX-G03505C
share

Covered type , Input 100 to 240 VAC , 35 W , Output 5 V 7 A , Front-mounting type
As of November 15, 2012
Power rating 35 W
Efficiency 73% Min.
Rated input voltage 100 to 240 VAC
Allowable-input voltage variable range 85 to 264 VAC80 to 370 VDC
Note at DC input The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency 50/60 Hz (47 to 450 Hz Single-phase)
Rated input current 1 A Max. ï¼ˆAt 100 VAC input)0.6 A Max. ï¼ˆAt 200 VAC input)
Leakage current 0.5 mA Max. (At 100 VAC input)1 mA Max. (At 200 VAC input)
Inrush current 20 A Max. ï¼ˆAt 100 VAC input (For cold start at 25 CEL))40 A Max. ï¼ˆAt 200 VAC input (For cold start at 25 CEL))
Rated output voltage 5 VDC
Output voltage variable range -10 to +15% (With V. ADJ)(If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.)
Ripple 2%(p-p) Max. (Under the rated I/O conditions.)
Static input variation influence 0.4% Max. (with AC input voltage)
Static load variation influence 0.8% Max. (At rated input, 0 to 100% load)
Ambient temperature variation influence 0.05 %/CEL Max. (At rated input/output voltage)
Rated output current 7 A
Start up time 500 ms Max. ï¼ˆUp to 90% of output voltage at rated input and output)
Hold time 20 ms Min. (At rated input voltage: 100 or 200 VAC at 100% load.)
Overload protection 105% to 175% of the rated output currentVoltage drop, Intermittent operation, Automatic reset
Overvoltage protection Operated at 120 to 140 % of the rated output voltage, Shut-offResetting: Reset the power by turning it back (OFF time: at least 7 min)
Overheat protection No
Maintenance forecast monitor output No
Total run time monitor output No
Undervoltage alarm output No
Power failure alarm output No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (Up to 2 Power Supplies with external diode)
Remote sensing function No
Applicable standard (UL) Standard No.: UL Listed: UL508 (Listing), UL UR: UL60950-1 (Recognition)
Applicable standard (CSA) Standard No.: cUL Listed: CSA C22.2 No.107.1, cUR: CSA C22.2 No.60950-1
Applicable standard (EN) Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMI)) Emission Enclosure: Conforms to EN55011 Group 1 Class AEmission AC mains: Conforms to EN55011 Group 1 Class A and based on FCC Class AEMS: EN61204-3 High severity levels
Applicable standard(VDE) Standard No.: VDE0160, VDE0805 Teil 1 File number:
Applicable standard(SEMI) F47-0200 (200 VAC input)
Applicable standard(Other) Conformed standard 2: Terminal block: Based on DIN EN50274 (VDE0660-514)
Ambient temperature Operating: -10 to 60 CELStorage: -25 to 65 CEL(with no icing or condensation)
Ambient humidity Operating: 25 to 85%Storage: 25 to 90%(With no icing or condensation)
Dielectric strength Between all inputs and all outputs: 3 kVAC for 1 min (Detection current: 20 mA)Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)Between all outputs and PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs and all inputs/ PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Natural air-cooling
Construction Covered type
Terminal type Screw terminal
Mounting type Front-mounting typeBottom-mounting typeSide-mounting type
Attachment Front-mounting Bracket
Weight 270 g Max.

Omron S8JX Switch Mode Power S8JX-P05012D
Omron S8JX Switch Mode Power S8JX-P05012D
Open-Frame Type , Input 100 to 240 VAC , 50W , Output 12V 4.2A , DIN Rail mounting typePower rating 50 WEfficiency 76% Min.Rated input voltage 100 to 240 VACAllowable-inp
Omron Power Supply S8VM Series S8VM-01515CD
Omron Power Supply S8VM Series S8VM-01515CD
Standard Type , Covered Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 15 W , Output 15 V 1 APower rating 15 WEfficiency 78% Min.Rated inpu
Omron Power Supply S8JX Switch Mode Power S8JX-G10048
Omron Power Supply S8JX Switch Mode Power S8JX-G10048
Open-Frame Type , Input 100 to 240 VAC , 100W , Output 48V 2.1A , Front-mounting typePower rating 100 WEfficiency 83% Min.Rated input voltage 100 to 240 VACAllowable-input vol
Omron Power Supply S8TX Series S8TS-03012F
Omron Power Supply S8TX Series S8TS-03012F
Basic Block , Connector Terminal Type , Input 100 to 240 VAC , Output 12 V 2.5 APower rating 30 WEfficiency 73% TYP. ï¼ˆAt rated input, 100% load)Rated input volt
Omron S8JX Switch Mode Power S8JX-G05048CD
Omron S8JX Switch Mode Power S8JX-G05048CD
Covered type , Input 100 to 240 VAC , 50 W , Output 48 V 1.1 A , DIN Rail mounting typePower rating 50 WEfficiency 82% Min.Rated input voltage 100 to 240 V
Omron Power Supply S8VM Series S8VM-05012CD
Omron Power Supply S8VM Series S8VM-05012CD
Standard Type , Covered Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 50 W , Output 12 V 4.3 APower rating 50 WEfficiency 79% Min.Rated in
Omron S8JX Switch Mode Power S8JX-G03515
Omron S8JX Switch Mode Power S8JX-G03515
Open-Frame Type , Input 100 to 240 VAC , 35W , Output 15V 2.4A , Front-mounting typeAs of November 15, 2012Power rating 35 WEfficiency 73% Min.Rated input voltage 100 to&
Omron Power Supply S8VM Series S8VM-10024C
Omron Power Supply S8VM Series S8VM-10024C
Standard Type , Covered Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 100 W , Output 24 V 4.5 APower rating 100 WEfficiency 82% Min.Rated 
Omron Power Supply S8EX Series S8EX-N01512
Omron Power Supply S8EX Series S8EX-N01512
Open type , Input 100 to 240 VAC , 15W , Output 12V 1.3APower rating 15 WEfficiency 77% Min. ï¼ˆAt 100 VAC input)77% Min. ï¼ˆAt 200 VAC input)Rated inpu
Omron Power Supply S8VS Series S8VS-06024A
Omron Power Supply S8VS Series S8VS-06024A
Maintenance Forecast Monitor Type , Input 100 to 240 VAC , 120 W , Output 24 V 5 A , With Undervoltage Alarm (Ttransistor (Sourcing))Power rating 120 WEfficiency 83%