Specifications:
INPUT
Rated power 20000 VA
Voltage 400 Vac three-phase + N Vac
Voltage tolerance ± 20%
Frequency tolerance 40/72 Hz
Power factor 0.99
BY PASS
Rated voltage 400
Voltage tolerance ± 15% (selectable from ± 5% to ± 25%)
Rated frequency 50/60 Hz
Frequency tolerance ± 5% (selectable from ± 0.25% to ± 10%)
Number phases 3
OUTPUT and INVERTER OUTPUT
Rated power 20000 VA
Active power 18000 W
Output current 29 A
Number phases 3
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Static stability ± 1%
Dynamic stability ± 3% in 10 ms
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load 3%
Voltage distortion with linear load 1%
Overload 125% 150% 168% of the rated current for 10' / 1' / 5

Riello Master MPS UPS MPT 160
Riello Master MPS UPS MPT 160
Specifications: INPUT Voltage 380 - 400 - 415 Vac three-phase Vac Frequency 45 - 65 Hz Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel) Soft start 0 - 100% in 120’’ (selectable) Voltage Range 400 V + 20% /- 25% BY PASS Rated voltage 380 - 400 - 415 Vac three-ph
Riello Sentinel Dual (High Power) UPS SDL 10000
Riello Sentinel Dual (High Power) UPS SDL 10000
Specifications:INPUTRated power 10000 VAVoltage 220-230-240 VacFrequency 50/60 Hz ± 5 HzPower factor >0.98Current distorsion ≤5%BY PASSVoltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)Frequency tolerance Selected frequency ± 5% (user configurable)OUTPUT and INVERT
Riello Net Power UPS NPW 2000
Riello Net Power UPS NPW 2000
Specifications: NPUT Rated power 2000 VA Voltage 220-240 Vac Voltage tolerance 230 Vac (+ 20 / - 26%) Frequency 50/60 Hz auto sensing OUTPUT and INVERTER OUTPUT Rated power 2000 VA Active power 1200 W Wave form on battery Pseudo sinewave Frequency on battery operation 50 or 60 Hz (± 0.5%)
Riello Sentinel Dual (High Power) UPS SDL 8000 TM
Riello Sentinel Dual (High Power) UPS SDL 8000 TM
Specifications:INPUTRated power 8000 VAVoltage 380-400-415 VacFrequency 50/60 Hz ± 5 HzPower factor >0.98Current distorsion ≤5%BY PASSVoltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)Frequency tolerance Selected frequency ± 5% (user configurable)OUTPUT and INVERTE
Riello Master HP UL UPS MHT UL 125
Riello Master HP UL UPS MHT UL 125
Specifications: Input voltage and frequency 480 VAC Three phase - 45~65 Hz ±2% selectable from ±1% to ±5% from front panel Output voltage ans frequency 380, 400, 415 VAC Three phase - 50/60 Hz (selactable Waveform Sinusoidal Power(KVA/KW)125/112.5 %Input voltage distoration (THDi) <3 Out
Riello Sentinel Power Green UPS SPH 10 ER
Riello Sentinel Power Green UPS SPH 10 ER
Specifications:INPUTVoltage 220-230-240 VacFrequency 50/60 Hz +/- 10 HzBY PASSVoltage tolerance 160 - 276 Vac (selectable in Economy Mode or Smart Active Mode)Frequency tolerance Selected frequency ±10%OUTPUT and INVERTER OUTPUTRated power 10000 VAActive power 9000 WWaveform Sinusoidal
Riello Sentinel Dual (High Power) UPS SDL 4000
Riello Sentinel Dual (High Power) UPS SDL 4000
Specifications:INPUTRated power 4000 VAVoltage 220-230-240 VacFrequency 50/60 Hz ± 5 HzPower factor >0.98Current distorsion ≤7%BY PASSVoltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)Frequency tolerance Selected frequency ± 5% (user configurable)OUTPUT and INVERTE
Riello Multi Guard Industrial UPS GMI 160
Riello Multi Guard Industrial UPS GMI 160
Specifications:INPUTFrequency tolerance between 40 Hz and 72 HzPower factor >0.99BY PASSRated voltage 220-230-240 Vac, single-phase + NOUTPUT and INVERTER OUTPUTRated power 20000 VAActive power 18000 WFrequency 50 Hz / 60 HzENVIRONMENTALNoise from ≤ 52 dBA to ≤ 70 dBADATADimensions (h w d) 745 x
Riello Master MPS UPS MPM 40
Riello Master MPS UPS MPM 40
Specifications:INPUTVoltage 380 - 400 - 415 Vac three-phase VacFrequency 45 - 65 HzFrequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)Soft start 0 - 100% in 120’’ (selectable)Voltage Range 400 V + 20% /- 25%BY PASSRated voltage 360-400-420 Vac three-phase + NRated frequen
Riello Multi Sentry UPS MST 120
Riello Multi Sentry UPS MST 120
Specifications:INPUTRated power 120000 VAVoltage 400 Vac three-phase + N VacVoltage tolerance ± 20%Frequency tolerance 40/72 HzPower factor 0.99BY PASSRated voltage 400Voltage tolerance ± 15% (selectable from ± 5% to ± 25%)Rated frequency 50/60 HzFrequency tolerance ± 5% (selectable from ± 0.2