Basic Block , Screw Terminal , Input 100 to 240 VAC , Output 24 V 2.5 A
Power rating 60 W
Efficiency 80% TYP. ï¼ˆAt rated input, 100% load)
Rated input voltage 100 to 240 VAC
Allowable-input voltage variable range 85 to 264 VAC80 to 370 VDC
Note at DC input The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency 50/60 Hz (47 to 63 Hz Single-phase)
Rated input current 1.0 A Max. ï¼ˆAt 100 VAC input)0.5 A Max. ï¼ˆAt 200 VAC input)
Power factor 0.9 Min. (At rated input, 100% load)
Harmonic Current EN61000-3-2
Leakage current 0.35 mA Max. (At 100 VAC input)0.7 mA Max. (At 240 VAC input)
Inrush current 17.5 A Max. ï¼ˆAt 100 VAC input (For cold start at 25 CEL))35 A Max. ï¼ˆAt 200 VAC input (For cold start at 25 CEL))
Rated output voltage 24 VDC
Output voltage variable range 22 to 28 V (With V. ADJ)
Ripple 2%(p-p) Max. (Under the rated I/O conditions.)
Static input variation influence 0.5% Max. (At 85 to 264 VAC input, 100% load)
Static load variation influence 3.5% Max. (Single operation, 0 to 100% load)2% Max. (Single operation, 10 to 100% load)5.5% Max. (Parallel operation, 0 to 100% load)3% Max. (Parallel operation, 10 to 100% load)
Ambient temperature variation influence 0.05 %/CEL Max.
Rated output current 2.5 A
Start up time 1000 ms Max. ï¼ˆ100/200 VAC, rated input)
Hold time 20 ms Min. (100/200 VAC, rated input)
Overload protection 105% to 140% of the rated output current (Single operation), 100% to 140% of the rated output current (Parallel operation)Inverted L voltage drop, Automatic reset
Overvoltage protection Operated at 120 to 145 % of the rated output voltage, Shut-offResetting: Reset the power by turning it back (OFF time: at least 1 min)
Maintenance forecast monitor output No
Total run time monitor output No
Undervoltage alarm output Yes (open collector output), 30 VDC Max., 50 mA Max.
Parallel operation Yes (Up to 4 Blocks)
N+1 redundant system Yes (Up to 5 Blocks)
Series operation Yes
Applicable standard (UL) Standard No.: UL508 (Listing, Class 2: Per UL1310), UL UR: UL60950-1 (Recognition)
Applicable standard (CSA) Standard No.: cUL Listed: CSA C22.2 No.107.1 (Class 2: Per No.223), cUR: CSA C22.2 No.60950-1
Applicable standard (EN) Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMI)) EMI: EN61204-3Emission Enclosure: Conforms to EN61204-3 Class BEmission AC mains: Conforms to EN61204-3 Class B and based on FCC Class AEMS: EN61204-3
Applicable standard(VDE) Standard No.: VDE0160, VDE0805 Teil 1 File number:
Ambient temperature Operating: -10 to 60 CELStorage: -25 to 65 CEL(with no icing or condensation)
Ambient humidity Operating: 25 to 85% RHStorage: 25 to 90% RH(With no condensation)
Dielectric strength Between all inputs and all outputs: 3 kVAC for 1 min (Detection current: 20 mA)Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)Between all outputs and PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs and all inputs/ PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Natural air-cooling
Construction Covered type
Structure Screw terminals
Mounting type DIN Rail mounting type
Weight 450 g Max.

Omron S8JX Switch Mode Power S8JX-P05048D
Omron S8JX Switch Mode Power S8JX-P05048D
Open-Frame Type , Input 100 to 240 VAC , 50W , Output 48V 1.1A , DIN Rail mounting typePower rating 50 WEfficiency 80% Min.Rated input voltage 100 to 240 VACAllowable-inp
Omron Power Supply S8VS Series S8VS-12024BE
Omron Power Supply S8VS Series S8VS-12024BE
Standard Model , Input 100 to 240 VAC , 30 W , Output 12 V 2.5 APower rating 30 WEfficiency 81% TYP. ï¼ˆAt 100 VAC input)80% TYP. ï¼ˆAt 200 VAC input)Rate
Omron Power Supply S8JX Switch Mode Power S8JX-G15012
Omron Power Supply S8JX Switch Mode Power S8JX-G15012
Open-Frame Type , Input 100 to 240 VAC , 150W , Output 12V 13A , Front-mounting typePower rating 150 WEfficiency 79% Min.Rated input voltage 100 to 240 VACAllowable-input volt
Omron S8JX Switch Mode Power S8JX-G01512
Omron S8JX Switch Mode Power S8JX-G01512
Open-Frame Type , Input 100 to 240 VAC , 15W , Output 12V 1.3A , Front-mounting typePower rating 15 WEfficiency 68% Min.Rated input voltage 100 to 240 VACAllowable-input volta
Omron Power Supply S8VM Series S8VM-03015C
Omron Power Supply S8VM Series S8VM-03015C
Standard Type , Covered Type , Bottom Mounting Type , Input 100 to 240 VAC , 30 W , Output 15 V 2 APower rating 30 WEfficiency 79% Min.Rated input voltage 100&n
Omron Power Supply S8JX Switch Mode Power S8JX-P10048C
Omron Power Supply S8JX Switch Mode Power S8JX-P10048C
Covered type , Input 100 to 240 VAC , 100W , Output 48V 2.1A , Front-mounting typePower rating 100 WEfficiency 81% Min.Rated input voltage 100 to 240 VACAllowable-input voltag
Omron S8JX Switch Mode Power S8JX-G03505D
Omron S8JX Switch Mode Power S8JX-G03505D
Open-Frame Type , Input 100 to 240 VAC , 35W , Output 5V 7A , DIN Rail mounting typeAs of November 15, 2012Power rating 35 WEfficiency 73% Min.Rated input voltage 10
Omron Power Supply S8VS Series S8VS-18024
Omron Power Supply S8VS Series S8VS-18024
Standard Model , Input 100 to 240 VAC , 180 W , Output 24 V 7.5 APower rating 180 WEfficiency 85% TYP. ï¼ˆAt 100 VAC input)88% TYP. ï¼ˆAt 200 VAC input)Ra
Omron S8JX Switch Mode Power S8JX-G05005
Omron S8JX Switch Mode Power S8JX-G05005
Open-Frame Type , Input 100 to 240 VAC , 50W , Output 5V 10A , Front-mounting typePower rating 50 WEfficiency 76% Min.Rated input voltage 100 to 240 VACAllowable-input voltage
Omron S8JX Switch Mode Power S8JX-G05024CD
Omron S8JX Switch Mode Power S8JX-G05024CD
Covered type , Input 100 to 240 VAC , 50 W , Output 24 V 2.1 A , DIN Rail mounting typePower rating 50 WEfficiency 83% Min.Rated input voltage 100 to 240 V